MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(b)(2) Hydraulic elevators Placed out of Service
|
x
|
x
|
Elevator is out of service.
|
|
conversion
|
conversion
|
n/a
|
|
|
Patch the holes in the left side hoistway wall between the first and second floor and near the pit light.
|
9/18/2018
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove all non-elevator related equipment from the machine room.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove all non-elevator related equipment from the machine room.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove object from door jamb to provide self-closing and self-locking of machine room door.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove object from door jamb to provide self-closing and self-locking of machine room door.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Seal all hoistway penetrations.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Seal all hoistway penetrations.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher in the elevator machine room is expired and shall be serviced or replaced.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher in the elevator machine room is expired and shall be serviced or replaced.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The in car emergency lighting shall be operational.
|
4/7/2020
|