MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered.
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.3.3.2(l)
|
x
|
|
Need to test the operation of emergency power.
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
8.7.3.31.5(c)(7) "ELEVATOR COMMUNICATIONS FAILURE" feature needs to be provided to verify operability of the telephone line.
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.19.15 Emergency Communications
|
x
|
|
8.7.3.31.5(c)(7)A visual indication on the same panel as the “PHONE” push button shall be provided, that is activated by authorized personnel, to acknowledge that two-way communications link has been established.
|
|
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.7.1.8
|
x
|
|
A data plate shall be provided as required by 8.6.1.5. In jurisdictions enforcing NBCC, the data plate required by 8.9.1 shall include the code and edition in effect at the time of alteration and the requirements in Section 8.7 that were applicable to the alteration.
|
|
|
A17.1-2016 : Elevators
|
2.30 - Hydraulic Power Unit
|
8.10.3.3.2(p)
|
x
|
|
8.7.3.31.5(c)(8) The elevator identification needs to be labeled on on both doorjambs of every elevator entrance at the designated level, alternate level, level where means necessary for tests is provided, and the driving machine.
|
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
3.8
|
x
|
|
8.7.3.8 The hydraulic line cannot be located in front the controller. Then area in front of the controller needs to be clear from the floor to the top of the controller 36" deep and 30" wide.
|
|