A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)(12) -
|
|
|
Fireman's light and audible needs to work.
|
5/13/2020
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Maintenance control program shall include current records of maintenance performed.
|
10/23/2020
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site maintenance control program.
|
2/11/2021
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site maintenance control records.
|
11/15/2021
|
A17.1-1996 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
1206.2(c)
|
|
|
Clean oil from car top, including car fan and ceiling fixtures.
|
11/15/2021
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean pit.
|
11/15/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency lights and alarm bell do not work.
|
11/15/2021
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Repair door detector, currently working off light/bell 110V circuit. When power is removed, it does not work.
|
11/15/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work, pushing button = nothing.
|
|
A17.1-1996 : Elevators
|
2.18 - Traction drive machines
|
1001.2(b)(16)
|
x
|
|
Drive sheave seals and worm shaft seals are worn and leaking. Repair as needed.
|
11/15/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)(12)
|
x
|
x
|
Phase 2 is not working, hold does not work, fireman's in car light and buzzer not working. Must be repaired within 30 days, reinspected by October 9th or unit will be red tagged.
|
10/13/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not have 2-way communication.
|
10/13/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phase Ii does not work
|
8/30/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phase I light and buzzer not working
|
8/30/2018
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)(12)
|
x
|
x
|
Repair firefighters service phase II so that it operates as intended. Hold does not work. Did not red tag unit. Reinspect only.
|
8/2/2019
|