MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell in car
|
10/6/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
|
|
Emergency light not working
|
9/17/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests)
|
|
|
Need testing procedures included in the MCP on or before 1/1/22
|
11/24/2021
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Oil leaking from machine room onto top of car through ceiling into cab
|
9/17/2018
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service test and document on log in machine room
|
3/13/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair alarm bell in car
|
12/2/2024
|
A17.1-1996 : Elevators
|
1.4 - Sills and car floor
|
204.2(a) Material for Car Enclosure Linings, and floor Coverings.
|
|
|
Replac broken loor tile at 2nd floor lobby car entrance (tripping hazard)
|
11/27/2019
|