Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Cartop needs to be cleaned 7/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Maintenance control program records need to be updated, including monthly fire service checks 7/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Valve leaking Oil back into tank. Repair or replace as needed. 8/31/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned 7/9/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No No fire service instructions next to key switch inside elevator cab 7/9/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 4/26/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV needs to be tested on or before next annual inspection. 12/12/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit not working properly at the time of inspection. 6/16/2025
MO Minimum : Elevators 2.3 - Lighting and receptacles 110.27 Guarding of Live Parts NFPA 72 No No Repair lights in machine room, wires are exposed. One light is out and fixture or bulbs need to be guarded 7/9/2024
A17.1-1996 : Elevators 2.35 - Supply Line and Shutoff Valve 303 No No A hydraulic fitting in the machine room is leaking excessively and shall be repaired. 6/9/2020
A17.1-1996 : Elevators 2.4 - Machine space 101.2 No No Remove non elevator related materials from machine room 7/9/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) No No The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 6/9/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 Yes No The fireman's emergency service phase I and II operations could not be tested. The elevator door operator was malfunctioning and the maintenance provider placed the unit out of service. 11/20/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No No fire service instructions next to key switch inside elevator cab 7/9/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No No fire service instructions next to key switch inside elevator cab. Re-inspection required 7/9/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 7/9/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate shall be displayed in elevator machine room. 8/31/2025