Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop needs to be cleaned 7/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Maintenance control program records need to be updated, including monthly fire service checks 7/9/2024
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned 7/9/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No fire service instructions next to key switch inside elevator cab 7/9/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required 4/26/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV needs to be tested on or before next annual inspection. 12/12/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit not working properly at the time of inspection.
MO Minimum : Elevators 2.3 - Lighting and receptacles 110.27 Guarding of Live Parts NFPA 72 Repair lights in machine room, wires are exposed. One light is out and fixture or bulbs need to be guarded 7/9/2024
A17.1-1996 : Elevators 2.35 - Supply Line and Shutoff Valve 303 A hydraulic fitting in the machine room is leaking excessively and shall be repaired. 6/9/2020
A17.1-1996 : Elevators 2.4 - Machine space 101.2 Remove non elevator related materials from machine room 7/9/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 6/9/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x The fireman's emergency service phase I and II operations could not be tested. The elevator door operator was malfunctioning and the maintenance provider placed the unit out of service. 11/20/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No fire service instructions next to key switch inside elevator cab 7/9/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No fire service instructions next to key switch inside elevator cab. Re-inspection required 7/9/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 7/9/2024