MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unit not working properly at the time of inspection.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
7/9/2024
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed.
|
6/9/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
The fireman's emergency service phase I and II operations could not be tested. The elevator door operator was malfunctioning and the maintenance provider placed the unit out of service.
|
11/20/2019
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.2
|
|
|
Remove non elevator related materials from machine room
|
7/9/2024
|
MO Minimum : Elevators
|
2.3 - Lighting and receptacles
|
110.27 Guarding of Live Parts NFPA 72
|
|
|
Repair lights in machine room, wires are exposed. One light is out and fixture or bulbs need to be guarded
|
7/9/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
4/26/2023
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
No fire service instructions next to key switch inside elevator cab. Re-inspection required
|
7/9/2024
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
No fire service instructions next to key switch inside elevator cab
|
7/9/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
No fire service instructions next to key switch inside elevator cab
|
7/9/2024
|
A17.1-1996 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
303
|
|
|
A hydraulic fitting in the machine room is leaking excessively and shall be repaired.
|
6/9/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
7/9/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Maintenance control program records need to be updated, including monthly fire service checks
|
7/9/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Cartop needs to be cleaned
|
7/9/2024
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV needs to be tested on or before next annual inspection.
|
12/12/2022
|