Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)1 Turn down fire tabs on all hoistway doors.
MO Minimum : Elevators (D) - Brakes (D)2 x x Test brake with 125% rated load. Did not red tag. 10/21/2019
MO Minimum : Elevators (E) - Machines (E)1 Traction machine is making a loud noise and vibrating. Repair
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) Ropes failed gauge test needs replacing
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Replace hoist ropes, red rouge reduced diameter within 30 days 5/13/2024
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Test car and counterweight buggers at rated speed. Did not red tag. 10/21/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need maintenance control program on site
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room