Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service testing and document on log in machine room 9/23/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test and document on log in machine room. 9/23/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need maintenance control program on site 9/23/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 9/23/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 9/23/2025
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)2 x x Re inspection: Completing 5 year test - Safeties Failed. Red Tag Still In Place
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Install guard on pit light 9/23/2025
MO Minimum : Elevators (I) - Pits (I)2 x x Repair or replace car buffer for proper operation. Frozen by rust. 9/23/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Repair broken mirror in elevator cab. 9/23/2025
MO Minimum : Elevators (A) - Hoistways (A)1 Turn down fire tabs on all hoistway doors. 9/23/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Complete 5 year test. 9/23/2025