Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 3.8 Traveling cable shall be replaced due to the cracking insulation and wires showing, creating a electrical hazard.
MO Minimum : Elevators (I) - Pits (I)1 Remove standing water from pit. 10/15/2019
MO Minimum : Elevators (A) - Hoistways (A)6 Repair loose and damaged retiring cam belt, rear. 10/15/2019
MO Minimum : Elevators (A) - Hoistways (A)10 Pull chain lock box is broken.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work
MO Minimum : Elevators (A) - Hoistways (A)10 Bottom floor pull chain box wont lock
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is not fire service instructions in car or on main landing