Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2 Install pit overflow bucket or oil recovery tank. 10/23/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Perform jack pressure relief test. 10/11/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Perform system leak-down test. 10/11/2019
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean & dry, there is oil in pit 12/23/2022
MO Minimum : Elevators (F) - Electrical Switches (F)1 x Repair broken c.o.p. stop switch 10/11/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance System low on oil. Car struggles to make a top terminal floor run. Gland packing leaking, replace. 10/23/2019