Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)8 Repair sump pump
MO Minimum : Elevators 2.3 - Lighting and receptacles 110.27 Guarding of Live Parts NFPA 72 Replace missing guards on machine room lights or provide tubes.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Clean all debris out of pit
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Bolt shut 8th floor rear door so that it will not open. Door is not in use
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Safety light ray does not work. Door will not reopen with something in the way. Reinspect Required
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) In car rear door is off track and needs to be reattached and locked shut
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code Replace missing guards on machine room lights or provide tubes
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Replace cab light that has open wiring. Replace missing covers on cab lights
MO Minimum : Elevators (F) - Electrical Switches (F)5 x Repair or replace damaged control switches. 9/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair emergency phone 9/29/2021
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x Suspension ropes are undersized. Reinspect in 120 days 1/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Shorten hoist cables. Counterweight stricking buffers before final limit 14 day reinspection 11/14/23 10/17/2024