A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Bolt shut 8th floor rear door so that it will not open. Door is not in use
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean all debris out of pit
|
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
In car rear door is off track and needs to be reattached and locked shut
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair emergency phone
|
9/29/2021
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)5
|
x
|
|
Repair or replace damaged control switches.
|
9/29/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Repair sump pump
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Replace cab light that has open wiring. Replace missing covers on cab lights
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Replace missing guards on machine room lights or provide tubes
|
|
MO Minimum : Elevators
|
2.3 - Lighting and receptacles
|
110.27 Guarding of Live Parts NFPA 72
|
|
|
Replace missing guards on machine room lights or provide tubes.
|
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Safety light ray does not work. Door will not reopen with something in the way. Reinspect Required
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Shorten hoist cables. Counterweight stricking buffers before final limit 14 day reinspection 11/14/23
|
10/17/2024
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Suspension ropes are undersized. Reinspect in 120 days
|
1/12/2023
|