MO Minimum : Elevators
|
(A) - Hoistways
|
(A)5
|
|
|
Pull straps shall be installed on hoistway doors & car gate
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Call cancel does not cancel call to floors 7,8,9 on Phase II, and recall does not work after coming off Phase II.
|
9/23/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light and alarm do not work.
|
9/23/2020
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)6
|
x
|
x
|
Safeties will not set. Kept pulling through governor. Red tagged elevator.
|
9/23/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light and alarm bell do not work.
|
12/21/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Suspension ropes are undersized. 90 day Re-inspection required
|
11/15/2022
|