A17.1-1996 : Elevators
|
3.8 - Top emergency exit
|
1001.2(c)(12)
|
|
|
Repair escape hatch switch that is disabled and removed from its position.
|
10/21/2019
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light inoperative.
|
5/1/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm inoperative.
|
5/1/2020
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Suspension ropes are undersized. 60 day repair/reinspection.
|
12/21/2020
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Door restrictor shall be made operable. Re-inspection required. This is the second notice
|
10/16/2023
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
x
|
|
Shorten ropes 5", runby had to move finally for it to work
|
11/15/2022
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
x
|
|
Unit only has 4 1/4" runby and it needs 6". Top final had to be moved. Re-inspection required with in 30 days. This is the second notice
|
10/16/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Door restrictor is not working. Re-inspection required, 2nd notice
|
10/29/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Various floors need the fire tabs bent down
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Door restrictor has been made inoperable. Re-inspection required
|
11/15/2022
|