Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The emergency power indicator light shall activate when unit is operating on emergency power. 7/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The emergency power indicator light shall activate when unit is operating on emergency power. 7/10/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The standby/emergency power indicator light at the egress floor shall illuminate when on emergency power operation. 3/6/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 2/22/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The means to restrict opening of the car door shall be operational. 3/6/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Car door restrictor is missing. 7/15/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency phone is hard to hear due to static. Take corrective action as needed. 1/24/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency phone is hard to hear due to static. Take corrective action as needed. 2/22/2022
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 1001.2(b)(11) Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed. 7/10/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including onsite documents. 7/10/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. 7/10/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Car tops shall be kept clean. Clean the car top. 7/10/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) 1206.2c - Clean the car top. 10/8/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The car top is dirty. Clean the car top. 7/10/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Pits shall be kept clean. Clean the pit. 7/10/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. 7/10/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/10/2024