A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
2/22/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency phone is hard to hear due to static. Take corrective action as needed.
|
2/22/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency phone is hard to hear due to static. Take corrective action as needed.
|
1/24/2023
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
1001.2(b)(11)
|
|
|
Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed.
|
7/10/2024
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Car tops shall be kept clean. Clean the car top.
|
7/10/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Pits shall be kept clean. Clean the pit.
|
7/10/2024
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
The means to restrict opening of the car door shall be operational.
|
3/6/2024
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Car door restrictor is missing.
|
7/15/2024
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
1206.2c - Clean the car top.
|
10/8/2019
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2c (Clean Car Tops)
|
|
|
The car top is dirty. Clean the car top.
|
7/10/2024
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site.
|
7/10/2024
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
The standby/emergency power indicator light at the egress floor shall illuminate when on emergency power operation.
|
3/6/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
7/10/2024
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide a code compliant MCP including onsite documents.
|
7/10/2024
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
|
7/10/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The emergency power indicator light shall activate when unit is operating on emergency power.
|
7/10/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
The emergency power indicator light shall activate when unit is operating on emergency power.
|
7/10/2024
|