Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Water damaged Pit equipment shall be replaced: Car and CW C-Channels, bottom of T-rails and pit ladder. 11/2/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 3.23/2.20.9.8 : Suspension rope shackles while have “anti-rotation” device installed. Shall be substantial in construction. 1/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers 2021 & 2022 VIO: G/2.7.1/8.6.1.6.5: Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 2018) 1/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates 2.13, 2.29.2, 5.9.2 : 5yr Test tags shall be current and installed on Governor, Safeties(Releasing carrier), Buffers. 1/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) 1/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers G/2.7.1/8.6.1.6.5: Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired) 5/18/2021
MO Minimum : Elevators (A) - Hoistways (A)16 I(6) Pit outlet not working, pit sump not working 1/12/2023