MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
G/2.7.1/8.6.1.6.5: Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired)
|
5/18/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
Water damaged Pit equipment shall be replaced: Car and CW C-Channels, bottom of T-rails and pit ladder.
|
11/2/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
3.23/2.20.9.8 : Suspension rope shackles while have “anti-rotation” device installed. Shall be substantial in construction.
|
1/12/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
2021 & 2022 VIO: G/2.7.1/8.6.1.6.5: Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 2018)
|
1/12/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
I(6) Pit outlet not working, pit sump not working
|
1/12/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
2.13, 2.29.2, 5.9.2 : 5yr Test tags shall be current and installed on Governor, Safeties(Releasing carrier), Buffers.
|
1/12/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized)
|
1/12/2023
|