Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 6/20/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x perform testing of emergency generator power operation 1/12/2024
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x x While conducting test of counterweight buffer, two suspension ropes jumped off sheave. Reg tagged elevator. 8/2/2021