Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency light does not work. 6/22/2020
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 1001.2(b)(29) x x While setting car safeties they broke causing car to become inoperable. Red tagged elevator. 8/5/2021
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 1001.2(b)(29) x x While setting car safeties they broke causing car to become inoperable. Red tagged elevator. 9/3/2021
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x The emergency car lighint i snot opeational, liley indicating that the back-up power device (battery) has failed. The fixute shall be repaired to operate. Re-inspect y 7/16/203 (30 days) 1/12/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The generator power on this 5 car bank needs to be tested. The transfer switch in the machine room indicates that the elevators are being supplied with generator power. Re-inspection required 4/26/2024
MO Minimum : Elevators (A) - Hoistways (A)16 The cover on the comp rope sheave switch is missing the cover 8/1/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 6/20/2024