Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(C) Repair inoperative stop switch cover warning buzzer. 1/7/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.4 Escalator Combplates Two comb teeth are broken at the lower end. 2/17/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x At least two demarcation light at both ends, with green lights, must be operational. Re-inspection required 6/5/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(A) x x Brake torque (measured at 20 ftlbs) is below the manufacturer’s minimum (55 ftlbs) value indicated on the brake tag. Brake does not meet required holding torque and must be repaired/replaced to comply with manufacturers specifications. 2/17/2026