Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(C) No No Repair inoperative stop switch cover warning buzzer. 1/7/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.4 Escalator Combplates No No Two comb teeth are broken at the lower end. 2/17/2026
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting Yes No At least two demarcation light at both ends, with green lights, must be operational. Re-inspection required 6/5/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(A) Yes Yes Brake torque (measured at 20 ftlbs) is below the manufacturer’s minimum (55 ftlbs) value indicated on the brake tag. Brake does not meet required holding torque and must be repaired/replaced to comply with manufacturers specifications. 2/17/2026