Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.11.5.2(i) Demarcation lighting
|
x
|
|
At least two demarcation light at both ends, with green lights, must be operational. Re-inspection required
|
6/5/2024
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(A)
|
x
|
x
|
Brake torque (measured at 20 ftlbs) is below the manufacturer’s minimum (55 ftlbs) value indicated on the brake tag. Brake does not meet required holding torque and must be repaired/replaced to comply with manufacturers specifications.
|
2/17/2026
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(C)
|
|
|
Repair inoperative stop switch cover warning buzzer.
|
1/7/2022
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.4 Escalator Combplates
|
|
|
Two comb teeth are broken at the lower end.
|
2/17/2026
|