MO Minimum : Elevators
|
(I) - Pits
|
(I)3
|
x
|
|
The counterweight guard shall extend not more than 12" above the pit floor to a point not less than 7' above the pit floor.
|
4/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed.
|
4/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
x
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
4/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
6/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
2.20
|
x
|
|
2.20.9.5.4 - The suspension rope retaining clips; the 1st clip shall be placed 4 times the diameter of the rope above the socket, the 2nd clip shall be 8 times the rope diameter above the 1st clip.
|
4/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4 Access to Pit
|
x
|
|
The pit ladder shall extend 48" above the landing sill.
|
4/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
A record of findings for firefighters service operation required by 8.6.11.1 with identification of the person(s) that performed operation shall be available on-site.
|
6/9/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
6/3/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post the current state operating certificate in the elevator machine room.
|
4/27/2020
|