Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. The voice works, but video/text not working properly, answering person cannot activate camera or text/screen.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications Yes No Emergency communications loss montior shall work properly. Buzzer does not sound.
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 Yes No Rope gripper wear switch indicates gripper break pads need to be replaced. Will not reset without assistance.
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current State operating certificate shall be displayed in the equipment room in a non-combustible frame.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Fire service testing must be properly documented monthly on the log sheet located in the MCP. Last documented 9/2024.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post the current state operating certificate in the elevator machine room. 4/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit Yes No The pit ladder shall extend 48" above the landing sill. 4/9/2021
MO Minimum : Elevators (I) - Pits (I)3 Yes No The counterweight guard shall extend not more than 12" above the pit floor to a point not less than 7' above the pit floor. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 Yes No 2.20.9.5.4 - The suspension rope retaining clips; the 1st clip shall be placed 4 times the diameter of the rope above the socket, the 2nd clip shall be 8 times the rope diameter above the 1st clip. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Yes No Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Yes No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 6/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No A record of findings for firefighters service operation required by 8.6.11.1 with identification of the person(s) that performed operation shall be available on-site. 6/9/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/3/2024