Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. The voice works, but video/text not working properly, answering person cannot activate camera or text/screen. 5/21/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications Yes No Emergency communications loss montior shall work properly. Buzzer does not sound. 5/21/2026
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 Yes No Rope gripper wear switch indicates gripper break pads need to be replaced. Will not reset without assistance. 5/21/2026
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current State operating certificate shall be displayed in the equipment room in a non-combustible frame. 5/21/2026
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Fire service testing must be properly documented monthly on the log sheet located in the MCP. Last documented 9/2024. 5/21/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. The voice works, but video/text not working properly, answering person cannot activate camera or text/screen.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications Yes No Emergency communications loss montior shall work properly. Buzzer does not sound.
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Yes No Current State operating certificate shall be displayed in the equipment room in a non-combustible frame.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Yes No Fire service testing must be properly documented monthly on the log sheet located in the MCP. Last documented 9/2024.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 Yes No 2.20.9.5.4 - The suspension rope retaining clips; the 1st clip shall be placed 4 times the diameter of the rope above the socket, the 2nd clip shall be 8 times the rope diameter above the 1st clip. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Yes No Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Yes No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 6/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No A record of findings for firefighters service operation required by 8.6.11.1 with identification of the person(s) that performed operation shall be available on-site. 6/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit Yes No The pit ladder shall extend 48" above the landing sill. 4/9/2021
MO Minimum : Elevators (I) - Pits (I)3 Yes No The counterweight guard shall extend not more than 12" above the pit floor to a point not less than 7' above the pit floor. 4/9/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post the current state operating certificate in the elevator machine room. 4/27/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/3/2024