Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x car door restrictor does not function. 4/12/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate 11/28/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x EMERGENCY LIGHT AND ALARM BELL DID NOT WORK
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light and bell do not operate 7/8/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light does not illuminate 11/28/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone dials out but disconnects. Phone begins dialing alternate numbers but there is no answer. 2/13/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 1/26/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate. 1/13/2023
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 100.7 FLOOR NUMBERS REQUIRED ON INSIDE OF HOISTWAY DOORS
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) Hall firefighter keyswitch identification markings are illegible. 3/21/2023
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) hall firefighter keyswitch identification markings are illegible. "on-off-byp" 3/15/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No current state operating certificate displayed in machine room 3/21/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No maintenance control plan on site 3/21/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No maintenance records on site 3/21/2023
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x Perform testing of overspeed valve 1/26/2023
A17.1-1996 : Elevators 2.14 - Code data plate 215 Post code data plate on controller or disconnect 3/21/2023
A17.1-1996 : Elevators 2.14 - Code data plate 215 Post code data plate on controller or disconnect 11/2/2023
A17.1-1996 : Elevators 2.14 - Code data plate 215 post code data plate on controller or disconnect. 3/15/2021
A17.1-1996 : Elevators 2.14 - Code data plate 215 Post code data plate on controller or disconnect. ASME A17.1 1996 3/21/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) post emergency evacuation of passengers procedure form inside machine room. 3/15/2021
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Post In Case of Fire signage next to hall button fixture at each landing 3/21/2023
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space remove non elevator related material from machine room. 3/15/2021
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Replace illegible identification bezel on phase 1 firefighter keyswitch. 3/21/2023
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Testing is due of overspeed valve 3/21/2023