Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate on wall above lift.
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.1.2 Space between upper landing door and platform exceeds 3".
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.1.3 Space between lower landing door and platform exceeds 3/4".
ASME A18.1-2005 : Lifts & Chairlifts 2.1 - Runways 2.1.1.3 Remove door handle from the inside lower landing door, potential pinch point exists.
Missouri Minimum : Platform Lifts CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Post operating certificate on wall above unit when received.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 Space between upper landing door and platform exceeds 3"
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 Space between lower landing door and platform exceeds 3/4".
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 Emergency alarm not working.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 Remove door handle from the inside of the lower landing door, pinch point exists.
ASME A18.1-2005 : Lifts & Chairlifts 2.11 - Emergency Signals 2.11.1 x Emergency alarm not working. 12/20/2023