MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Remote set/reset function of governor does not work.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
The car door restrictor shall be operational.
|
5/13/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.4 Protection of Light Bulbs and Tubes
|
|
|
In car lighting shall be externally guarded or coated to contain broken glass in case the bulb or tube accidentally breaks.
|
5/13/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.4 Protection of Light Bulbs and Tubes
|
|
|
In car lighting shall be externally guarded or coated to contain broken glass in case the bulb or tube accidentally breaks.
|
5/13/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
No one answered the emergency phone. A two-way communications means between the car and a location staffed by authorized personnel shall be provided.
|
4/4/2025
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
3/22/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational on auxiliary power.
|
5/13/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
8.11.2.1.2(j)
|
|
|
Label the disconnects with the source panel location, panel designation and breaker number.
|
4/15/2019
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
The panel designation and breaker numbers feeding the main line disconnect shall be indicated on the disconnect.
|
4/15/2019
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
The panel designation and breaker numbers feeding the 110v disconnect shall be indicated on the disconnect.
|
4/15/2019
|
A17.1-1996 : Elevators
|
2.40 - Maintenance Records
|
210.1d Inspection Operation.
|
|
|
Provide MCP in machine room.
|
4/15/2019
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Fire service testing shall be documented monthly.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
3/22/2022
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
3/22/2022
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Non-elevator related items shall not be stored in the machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
The fire extinguisher in the elevator machine room is expired and shall be replaced or serviced.
|
5/13/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Provide smoke detector(s) in secondary machine space and provide testing of smoke detectors.
|
4/15/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Provide heat detectors in secondary machine space and provide testing of heat detectors.
|
4/15/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/22/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
5/13/2020
|