MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Junction box for pit light on/ off switch has been damaged and has exposed electrical wiring, needs to be repaired
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car does not work when normal power is removed, needs repaired. Re-inspection required
|
2/13/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two way communication is not working. Re-inspection required
|
2/15/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Need to provide type ABC fire extinguisher in machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Drywall in machine room around air conditioning unit appears to have black mold. Mold should be abated and drywall replaced to restore fire rating to machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|