Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The width of the working space of the main elevator disconnect shall in no case be less than the width of the disconnect. A surge suppressor has been mounted directly under the handle and immediately next to the disconnect. With the handle in the open position, it hits the suppressor. It shall be moved to meet the clearance requirements of NFPA 110.26.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency lights shall be operational. 12/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The alarm bell shall operate on auxiliary power. 12/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The car top light shall be operational. 1/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records An MCP shall be in place as specified in A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 1/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 1/31/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 1/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The car top light shall be operational. 4/5/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The width of the working space of the main elevator disconnect shall in no case be less than the width of the disconnect. A surge suppressor has been mounted directly under the handle and immediately next to the disconnect. With the handle in the open position, it hits the suppressor. It shall be moved to meet the clearance requirements of NFPA 110.26. 1/29/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The car-top lighting shall be operational. (2nd Notice) 2/13/2025