Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Replace the car light as the tubes are burnt out. 9/25/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting REplace the burnt out light tubes in the car ceiling as 2 two are required to be working.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Replace the burnt out pit light 9/25/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Replace the faulty fire service key switch, as it is hard to get contact with the tumblers, otherwise the fire service works fine. 9/4/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.2 Minimum Illumination Replace the burnt out light sin the car.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair or replace the emergency phone as it will not dial out
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 9/25/2019
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Have the fire extinguisher re-certified
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean up the pit