Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b Yes No A temporary air conditioning unit has been installed in the machine room. Proper code compliant permanent ventilation is required. This is the 3rd consecutive year that this violation has been issued. A permanent means SHALL be made in 30 days or the elevator will be removed from service due to not having a current certificate of compliance. Reinspection is required for compliance,
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 1001.2(a)(16) No No There is no car capacity plate inside the elevator stating the rated load of the car, as required. 10/20/2020
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) No No The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 10/20/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No The emergency car lighting fixture is missing its protective cover. A protective cover plate shall be reinstalled for passenger safety. 10/20/2020
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) No No The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No The 4th floor is missing a pick up roller for the car door clutch to work properly. Replace missing pick up roller. 7/16/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No The position indicating or “PI” device in the car was not operational on the day of inspection. Repair “PI” device to indicate the position of the elevator car. 7/16/2026
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No A temporary air conditioning unit has been installed in the machine room. Proper code compliant permanent ventilation is required. 7/16/2026
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No A temporary air conditioning unit has been installed in the machine room. Proper code compliant permanent ventilation is required 7/16/2026