Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x The door open button, 8th, and 6th floor car call buttons are operating intermittently. Buttons inside of the elevator cab need to be functioning for emergency personnel
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Lights in elevator cabs need to be guarded or sleeved to prevent breakage
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) two damaged rollers on bottom of counterweight 12/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication. No dial tone. 12/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication 4/19/2024
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.6.4.20.11 (Re-Inspection) x Unable to perform 125% Emergency Brake Unintended Movement Test 4/19/2024