A17.1-2016 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
8.7.3.22.2
|
x
|
|
3.4.5Any horizontal area above the car enclosure top and within the railing if supplied which could contain a circle with a diameter of equal to or greater than 350 mm (14 in.) that does not have a vertical clearance of 1 100 mm (43 in.) when the car has reached its maximum upward movement shall be clearly marked. The marking shall consist of alternating 50 mm (2 in.) diagonal red and white stripes. In addition, when markings are provided, sign(s) with the words “DANGER LOW CLEARANCE” shall be prominently posted on the crosshead and be visible from the hoistway entrance(s).
|
8/10/2023
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
3.29
|
x
|
|
2.29.1.1 In buildings with more than one elevator, each elevator in the building shall be assigned a unique alphabetic, numeric, or alphanumeric identification. The identification (2inches minimum) shall be painted on, engraved on, or securely attached to or adjacent to the following equipment associated with each elevator or the enclosures housing the following equipment associated with each elevator: (a) the driving machine, (b)controller, (f) disconnecting means, (g) the crosshead, or where there is no crosshead, the car frame, such that it is visible from the hoistway landing (h) the car operating panel, a minimum of 13 mm (0.5 in.) in height (i) on both doorjambs of every elevator entrance at the designated level and alternate level
|
8/10/2023
|
A17.1-2016 : Elevators
|
3.27 - Crosshead Data Plate and Rope Data Tags
|
3.16
|
x
|
|
Update Crosshead Data Plate to reflect increase in rated speed
|
8/10/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The Emergency Phone in the car fails to establish two-way communication. No active dial tone.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered.
|
8/10/2023
|