MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working, needs repaired. Re-inspection required
|
1/23/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator cab phone is still not working. Re-inspection required
|
1/23/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work. Re-inspection required
|
5/7/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Light rays are not working, mechanical edge works. Repair/replace light rays. Re-inspection required
|
11/24/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Provide means to collect oil scavenged, return line into tank to be removed.(due to extreme depth of pit, place bucket in machine room)
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Door reopening device (light ray) does not work, needs repaired. Re-inspection required
|
5/7/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Re-inspection to check door re-opening device (light ray), still not working, needs repaired. Re-inspection required
|
1/23/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Car failed 15 minute stand test, tech determined leaking back through the valve. Repair or replace as needed.
|
|
conversion
|
conversion
|
n/a
|
|
|
Fire service key switch bezels not readable in car and hallway
|
2/19/2019
|
conversion
|
conversion
|
conversion - reinspect
|
|
|
Emergency phone not working
|
1/31/2019
|
conversion
|
conversion
|
n/a
|
|
|
Clean pit of debris
|
2/19/2019
|
conversion
|
conversion
|
n/a
|
|
|
Repair or replace electric eyes
|
2/19/2019
|
conversion
|
conversion
|
n/a
|
|
|
Do not use machine room as storage space
|
2/19/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current operating certificate in machine room.
|
2/19/2019
|