Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Fire service key switch bezels not readable in car and hallway 2/19/2019
conversion conversion conversion - reinspect Emergency phone not working 1/31/2019
conversion conversion n/a Clean pit of debris 2/19/2019
conversion conversion n/a Repair or replace electric eyes 2/19/2019
conversion conversion n/a Do not use machine room as storage space 2/19/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room. 2/19/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Light rays are not working, mechanical edge works. Repair/replace light rays. Re-inspection required 11/24/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working, needs repaired. Re-inspection required 1/23/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Re-inspection to check door re-opening device (light ray), still not working, needs repaired. Re-inspection required 1/23/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator cab phone is still not working. Re-inspection required 1/23/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door reopening device (light ray) does not work, needs repaired. Re-inspection required 5/7/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work. Re-inspection required 5/7/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Car failed 15 minute stand test, tech determined leaking back through the valve. Repair or replace as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Provide means to collect oil scavenged, return line into tank to be removed.(due to extreme depth of pit, place bucket in machine room)