Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be properly displayed in machine room. 7/24/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 9/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 11/8/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 5/15/2024
A17.1-1996 : Elevators 2.32 - Control Valve 303 x Car failed 15 minute stand test, technician determined that it is leaking back through the valve.
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Battery lowering system shall work. Reinspect required. 8/11/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Emergency battery lowering device does not work. 3/29/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x One bulb in emergency light does not work. 3/29/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance When unit was put on ring, excessive fluid leakage from top Vic fitting (below valve) or bottom of valve. Repair as needed. 7/24/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Replace bad light bulb in emergency light fixture. Reinspect required. 8/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone shall provide two way communications, no one answered. Reinspect required. 8/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Provide on-site maintenance control program. 7/24/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Need to replace bad light bulb in emergency light fixture. Re-inspection required 10/24/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone shall provide two way communication. Re-inspection required 10/24/2023