MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
need to have maintenance control program on site documents
|
3/3/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
monthly fire service test log had not been filled out since September
|
3/3/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, phone line was dead
|
3/31/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
|
|
fill out the monthly fire service test log monthly, has not been filled out since June 2022
|
1/5/2024
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Perform monthly fire service test and post a log in the machine room
|
5/25/2020
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.3.1.2(j)
|
|
|
machine room fire extinguisher inspection tag is expired
|
3/31/2022
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
could not lock the adjustment on the overspeed valve because it is rusted in place, could not seal the overspeed valve
|
1/5/2024
|