Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Perform monthly fire service test and post a log in the machine room 5/25/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log had not been filled out since September 3/3/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records need to have maintenance control program on site documents 3/3/2021
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.3.1.2(j) machine room fire extinguisher inspection tag is expired 3/31/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) fill out the monthly fire service test log monthly, has not been filled out since June 2022 1/5/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone did not work, phone line was dead 3/31/2022