Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 No No Debris in pit, remove. 1/16/2026
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 1001.2(a)(16) No No Need to post "C-1 Loading No Passengers" sign inside elevator. 1/16/2026
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 207 No No Need to post sign that says "C-1 LOADING NO PASSENGERS". Lettering to be a minimum of 1/2 inch high. 1/16/2026
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 207 No No Post "C-1LOADING. THIS ELEVATOR DESIGNED TO TRANSPORT LOADED INDUSTRIAL TRUCK. MAXIMUM COMBINED WEIGHT OF INDUSTRIAL TRUCK AND LOAD NOT TO EXCEED 10000 LB" 1/16/2026
A17.1-1996 : Elevators 1.9 - Power closing of doors or gates 112.3 No No During automatc closing of vertical sliding doors a warning bell shall sound until hoistway doors are fully closed. 1/16/2026
A17.1-1996 : Elevators 1.9 - Power closing of doors or gates 112.3 No No Warning bell shall sound during automatic closing of vertical doors until hoistway door is fully closed. 1/16/2026
A17.1-1996 : Elevators 1.9 - Power closing of doors or gates 112.3 No No Warning bell needs to sound during automatic closing until vertical bi-parting hoistway doors are fully closed 1/16/2026
A17.1-1996 : Elevators 2.14 - Code data plate 215 No No Post code data plate on controller or disconnect. "ASME A17.1 1996" 1/16/2026
A17.1-1996 : Elevators 2.14 - Code data plate 215 No No Post code data plate on controller or disconnect. "A17.1 1996" 1/16/2026
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No Machine room lighting does not illuminate 1/16/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No No MCP in machine room 1/16/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No No MRL in machine room 1/16/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No No MCP 1/16/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No No maintenance records on site 1/16/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No Post emergency evacuation of passengers form inside machine room 1/16/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Remove debris from pit 1/16/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Remove detris from pit 1/16/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Remove debris from elevator pit 1/16/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Remove wood pallet debris from pit 1/16/2026
A17.1-1996 : Elevators 5.4 - Normal terminal stopping devices 209 Yes No Replace broken lower normal terminal stopping switch. 9/13/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Test and log firefighter operation monthly 1/16/2026
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys No No All elevators in the same building shall have firefighter keyswitches operated by the same key. 9/14/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Test and log firefighter operation monthly 1/16/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate inside machine room 1/16/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 1/16/2026
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed in machine room 1/16/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state operating certificate inside the machine room 1/16/2026