A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.8 Switch Keys
|
|
|
All elevators in the same building shall have firefighter keyswitches operated by the same key.
|
9/14/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Debris in pit, remove.
|
|
A17.1-1996 : Elevators
|
1.9 - Power closing of doors or gates
|
112.3
|
|
|
During automatc closing of vertical sliding doors a warning bell shall sound until hoistway doors are fully closed.
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Machine room lighting does not illuminate
|
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
1001.2(a)(16)
|
|
|
Need to post "C-1 Loading No Passengers" sign inside elevator.
|
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
207
|
|
|
Need to post sign that says "C-1 LOADING NO PASSENGERS". Lettering to be a minimum of 1/2 inch high.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No maintenance records on site
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No MCP
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No MCP in machine room
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No MRL in machine room
|
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
207
|
|
|
Post "C-1LOADING. THIS ELEVATOR DESIGNED TO TRANSPORT LOADED INDUSTRIAL TRUCK. MAXIMUM COMBINED WEIGHT OF INDUSTRIAL TRUCK AND LOAD NOT TO EXCEED 10000 LB"
|
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
Post code data plate on controller or disconnect. "A17.1 1996"
|
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
Post code data plate on controller or disconnect. "ASME A17.1 1996"
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate inside machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the machine room
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Post emergency evacuation of passengers form inside machine room
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Remove debris from elevator pit
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove debris from pit
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove detris from pit
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Remove wood pallet debris from pit
|
|
A17.1-1996 : Elevators
|
5.4 - Normal terminal stopping devices
|
209
|
x
|
|
Replace broken lower normal terminal stopping switch.
|
9/13/2023
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed in machine room
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Test and log firefighter operation monthly
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Test and log firefighter operation monthly
|
|
A17.1-1996 : Elevators
|
1.9 - Power closing of doors or gates
|
112.3
|
|
|
Warning bell needs to sound during automatic closing until vertical bi-parting hoistway doors are fully closed
|
|
A17.1-1996 : Elevators
|
1.9 - Power closing of doors or gates
|
112.3
|
|
|
Warning bell shall sound during automatic closing of vertical doors until hoistway door is fully closed.
|
|