Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm bell is not working on battery back up. 12/12/2019
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 107.1b Yes No Provide correct runby clearance of counterweight. 9/29/2020
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) Yes No Suspension cables are rouged and undersized, need to replace cables. Re-inspection required
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No Emergency light is not working on battery back up. 12/12/2019
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No Permanent means of machine room temperature control are inoperable and shall be repaired in order to maintain temperature control. 10/28/2025
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No Service fire extinguisher in machine room. 10/14/2020