Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and related documentation shall be provided in the machine room. Fire service shall be documented monthly.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Car having issues running on automatic, performed as much of test as possible. Testing still needed for 125% brake test, 100% full speed safety test, slide, governor rope pullout, full speed car, and counterweight buffer test, door closing force, fire service, emergency light, emergency bell, and emergency phone.