A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Pit needs to be cleaned
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Pit light does not work
|
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
1001.2(c)(26)
|
x
|
|
Governor rope has grease all over it, should not be greased. Clean grease off rope. Re-inspection required
|
10/16/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Ropes have been replaced but got twisted during testing. Take corrective action and re-test. Unit left shut down by maintenance company.
|
10/16/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work. Re-inspection required
|
10/16/2024
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
212
|
x
|
|
Suspension ropes have rouge and are undersized. Re-inspection required
|
10/16/2024
|