Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current State Operating Permit shall be obtained and displayed in the Equipment Room.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/3/2026
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 107.1b Yes No Counterweight runby shall not be less than 6". Currently 1".
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. Re-inspection required 10/16/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No Fire Service Testing must be documented monthly in the MCP located in the machine room.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No Fire service testing must be documented monthly. 4/3/2026
A17.1-1996 : Elevators 3.20 - Governor rope 1001.2(c)(26) Yes No Governor rope has grease all over it, should not be greased. Clean grease off rope. Re-inspection required 10/16/2024
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d No No Machine room door shall be self-closing and self-locking and operable from the interior space without the use of a key. Door cannot be opened inside machine room. 4/3/2026
A17.1-1996 : Elevators 2.4 - Machine space 100.3d No No Machine room door shall be self-closing and self-locking. Door handle cannot be locked.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No Machine Room Fire Extinguisher shall have current monthly/annual test tag.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No Machine room lighting needs to be repaired, 1 or more bulbs not working.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No Machine room lighting needs to be repaired. One or more bulbs are not working. 4/3/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit light does not work 4/3/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit needs to be cleaned 4/3/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Pit shall be kept clean. Remove excess debris.
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 Yes No Replace missing Fire tab on 14R hoistway door.
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 No No Replace missing/damaged pickup rollers on 4R hoistway door.
A17.1-1996 : Elevators 3.27 - Crosshead data plate 212.2 No No Suspension ropes shall have proper data tag(s)
A17.1-1996 : Elevators 3.23 - Suspension rope 212 Yes No Suspension ropes have rouge and are undersized. Re-inspection required 10/16/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A code compliant MCP and related on-site documentation shall be provided in the machine room. 4/3/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/3/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Items to be completed: 100% Safety Set, Slide, 125% items.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self-closing and self-locking. 4/3/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Ropes have been replaced but got twisted during testing. Take corrective action and re-test. Unit left shut down by maintenance company. 10/16/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete. Items to be completed: door closing force, SOS, 100% Safety Set, Slide, 125% weight, Emergency light/bell/phone, runby. 2/18/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete. Items to still be tested: SOS, 100% safety set, 125% weight, emergency light/bell/phone, runby. 4/10/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete. Testing still needed: spin test on governor and switch, 125% brake test, full load safety test, emergency phone, emergency light, and emergency bell. 4/3/2026