Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(1) Electric elevator, dumbwaiter, or material lift Placed out of Service x x Complete 5 year testing..reinspection required within 14 days 9/16/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test emergency generator 9/16/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test Emergency generator reinspection required within 30 days
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log x Complete 5 yr test (Fire Service) Reinspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Repair emergency light in car 9/16/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) Rope grippers need repair 10/16/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need maintenance control program on site posted on controller 2/12/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Rope came out of the groove on the sheave at the top of the hoistway 2/11/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Need to include testing procedures in MCP on or before January 1,2022 9/17/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room 10/23/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Provide testing procedures in the maintenance control program 10/23/2024
MO Minimum : Elevators (I) - Pits (I)1 Clean pit, 10/23/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Replace hoist ropes red rouge reduced diameter 7/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Repair replace deflector sheave within 60 days 10/23/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Complete annual test within 14 days unintended motion alternate fire floor 7/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Repair emergency light and bell 7/21/2022