MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean pit
|
10/23/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Complete 5 yr test (Fire Service) Reinspection required
|
11/4/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Complete annul test within 14 days unintended motion alternate fire designated floor
|
7/21/2022
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Counterweight governor rope has to be replaced, severe rouge and multiple strands broken
|
1/18/2021
|
MO Minimum : Elevators
|
(G)2-Alterations
|
8.7.2.14.2 Car Enclosure
|
x
|
|
Emergency lights in car not working
|
11/27/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Need maintenance control program on site posted on controller
|
2/12/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Need to include testing procedures in MCP on or before January 1,2022
|
9/17/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service testing and document on log in machine room
|
10/23/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests)
|
|
|
Provide testing procedures in the maintenance control program
|
10/23/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Repair/replace deflector sheave within 60 days
|
10/23/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.2 Replacement of Suspension Means (Re-Inspection)
|
x
|
|
Replace hoist ropes (red rouge & reduced diameter)
|
9/18/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
Replace/Repair deflector sheave top of hoistway
|
9/18/2024
|
MO Minimum : Elevators
|
(J) - Counterweights
|
(J)3
|
|
|
Shackles on counterweights rubbing frame thin, need longer shackles.
|
12/5/2019
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
test emergency generator
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test emergency generator. Reinspection required within 30 days
|
11/4/2024
|