Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone inoperative. No voltage measured at incoming line. 6/11/2020
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform OSV test on or before next annual inspection. 6/22/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) Replace machine room door closer, shall be self-closing. 6/22/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Existing phone not working correctly, repair as needed. 11/2/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide MCP. 5/15/2023
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV (sealed,no tag) in pit due for testing. Provide per MFG, leave written procedures with MCP. Tag and seal upon completion. 11/2/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening. The door restrictor is missing parts 4/28/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The Emergency Phone in the car fails to establish two-way communication.