Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Remove scavenger unit from the pit.
MO Minimum : Elevators (I) - Pits (I)1 Remove the scavenger line.
MO Minimum : Elevators (I) - Pits (I)1 Remove oil from the sump hole.
MO Minimum : Elevators (I) - Pits (I)1 Determine if the sump pump works, if not replace.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)2 Alterations x Oil has water mixed in, replace oil.
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 x Provide bottom retainer, all hoistway doors.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph x Provide lobby warning placards, all landings.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits x Provide pit to be dry. Install sump cover.
conversion conversion n/a Current operating certificate shall be displayed. 8/6/2020